Reviewed by: Bergstrom, Leigh W. Permit #: C14-1404
Phone: 343-8326 Date: 6/04/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: CornellTA@muni.org
Project: Lush Fresh Handmade Cosmetics
Review Number: 331530
1) STATUS: 6-04-14 Comments to be addressed.
2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.
3) 2/A0.4 A side wall vertical grab bar is also required for an ADA water closet installation per ICC/ANSI A117.1-604.5.1.
4) 2/A2.2 Provide storefront glazing design and fastening details for structural review on a deferred submittal basis.
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.
RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.