Reviewed by: Bergstrom, Leigh W. Permit #: C13-1821 X14-1265
Phone: 343-8326 Date: 5/30/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska Regional Hospital 4th Floor Upgrades
Review Number: 331315
1) STATUS: 4-17-14 Comments to be addressed. 5-30-14 APPROVED.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 5-30-14.
3) M1.04B & M1.08 The "existing chase" is actually a 2-Hour rated shaft and the duct penetrations (entering and leaving) require FSD's. (IBC 716.5.3) RESOLVED PER RESUBMITTAL AND ALTERNATE MEANS REQUEST RECEIVED 5-09-14.
4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. RESOLVED 5-30-14.