Permit Number: C14-1396
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2925 DEBARR RD Anchorage
Location:
Work Description:

Comm T/I:  tenant improvement buildout of shell space, exam rooms, offices, out-patient procedure rooms, labs & reception areas / tb

PAID FOR (6) ADD'L INSPECTIONS 11/19/14

Status: Closed
Project Name: ALASKA UROLOGY
Review Type: Mechanical
Result: Approved
Result Date: 7/16/2014 8:35:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C14-1396

Phone: 343-8326                                                                           Date:7/16/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Alaska Urology 

Review Number: 331287

 

1) STATUS:   5-16-14 Comments to be addressed.          7-16-14 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.        RESOLVED 7-16-14.

 

3) M303          The two 30"x 30" RA ducts penetrating 2-Hour rated shafts require fire/smoke dampers per IBC 716.5.3.     IFC 406.3.3.2 ALLOWS EXISTING SHAFT PENETRATIONS/OPENINGS IF THE BUILDING IS FULLY SPRINKLERED. RESOLVED 7-16-14.

 

4) M303          The existing ducts penetrating the same shafts also require fire/smoke dampers per IBC 716.5.3. Please clarify.               IFC 406.3.3.2 ALLOWS EXISTING SHAFT PENETRATIONS/OPENINGS IF THE BUILDING IS FULLY SPRINKLERED. RESOLVED 7-16-14.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                   RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.        RESOLVED 7-16-14.

 

 