Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1369
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Comm T/I: interior luxury VIP scaring & finish retrofit to all auditoriums within existing cinema; works are limited to auditorium interiors; includes elec / tb
Status: Issued
Project Name: DIMOND CENTER 9
Review Type: Fire
Result: Approved
Result Date: 5/15/2014 4:26:39 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st Review 5/15/2014 - Corrections Required.

.

1.  Provide revised occuppant load signs as required per IBC 1004.3.  Show locations on plans.  Provide one for each auditorium at the vestibule entry and separate signage for the lobby and the entire theatre.  The lobby & theatre sign maybe combined.

.

New occuppant loads:  Auditorium #1= 40, #2=36, #3=43, #4=88, #5=58, #6=67, #7=47, #8=48, #9=48,  Lobby=150, Theatre Total = 466.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter