Reviewed by: Bergstrom, Leigh W. Permit #: C14-1332
Phone: 343-8326 Date: 5/02/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: CornellTA@muni.org
Project: Alaska Airlines HQ Roof Replace
Review Number: 330373
1) STATUS: 5-02-14 Comments to be addressed.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.
3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for ACU-1 & 2 EVAPORATOR, BLR-1 & 2, FCU-1 and RTU-1 to include engineers stamp and signature, for structural review on a deferred submittal basis.
4) RTU-1 requires a smoke detector per IMC 606.2. Please clarify.
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.