Building Safety Division
Fire system comments
Reviewed by: Mark Warren Permit #: f14-1073
Phone: 267-4992 Date: 4/21/2014 updated corrections 4/25/2014
Fax: 249-7397 9/29/2014, approved.
Email: warrenmj@mini.org
Permit Manager: Bob Parker
Phone: 343-8320
Email: parkerw@muni.org
Project: Dimond center common area fire alarm
Review Number: 329696
____________________________________________________________________________________
PERMIT STATUS: corrections
1) The owner needs to provide an agreement with fire prevention in regards to the milestones in place to complete the fire alarm system in all areas of the mall. Resolved.
2) Show smoke detection at all fire alarm, booster and amplifier panels required by NFPA 72 2010. Resolved
3) Provide a matrix showing all of the other fire alarm systems and there interface with the main alarm. Resolved
4) Show hall between hobby craft and pacific sun wear to be out of contract since it is not a common area. Resolved
5) Show the hall to the north by Billabong to be wired for a future enunciator. Resolved
6) Show an additional pull station on the north side of the wall that would be visible exiting from best buy. Resolved
7) Show the anunciator at the west entrance on page 12.5. Resolved
8) Show a pull station on the west exit of spaces 171, 167 and the hall directly to the north. Show an additional pull station on the south side of the escalator on page 12.8. Resolved
9) Show a correction on sheet 12.10 for forever 21 to reflect the correct construction. Resolved
10) Show a correction on sheet 12.11 for the hall on the bottom of the page to reflect the correct construction. Resolved
11) Show additional door and wall in hall with additional required coverage on page 12.21. Resolved
12) Show increase candela for speaker strobe in the hall on page 12.23.Resolved
13) On page 12.24 show additional fire door and wall on lower right side of page. Show what system the existing pull station is going to activate and any additional pull stations. Show door and wall with additional strobe coverage in hall behind Cali Nails. Resolved.
Mark Warren, Systems Plan Review