Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: F14-1073
Permit Type: Commercial Trade Permit - Alteration Fire
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: NEW FIRE ALARM SYSTEM FOR ALL COMMON AREAS OF PHASE 1 AND 2 OF THE DIMOND MALL - BWP
Status: Issued
Project Name:
Review Type: Fire System
Result: Approved
Result Date: 9/29/2014 3:19:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire system comments

 

Reviewed by: Mark Warren                                                        Permit #: f14-1073

Phone: 267-4992                                                                        Date: 4/21/2014 updated corrections 4/25/2014

Fax: 249-7397                                                                            9/29/2014, approved.

Email: warrenmj@mini.org

Permit Manager: Bob Parker

Phone: 343-8320

Email: parkerw@muni.org

Project: Dimond center common area fire alarm   

Review Number: 329696

____________________________________________________________________________________

 

PERMIT STATUS: corrections

1)      The owner needs to provide an agreement with fire prevention in regards to the milestones in place to complete the fire alarm system in all areas of the mall. Resolved.

2)      Show smoke detection at all fire alarm, booster and amplifier panels required by NFPA 72 2010. Resolved

3)      Provide a matrix showing all of the other fire alarm systems and there interface with the main alarm. Resolved

4)      Show hall between hobby craft and pacific sun wear to be out of contract since it is not a common area. Resolved

5)      Show the hall to the north by Billabong to be wired for a future enunciator. Resolved

6)      Show an additional pull station on the north side of the wall that would be visible exiting from best buy. Resolved

7)      Show the anunciator at the west entrance on page 12.5. Resolved

8)      Show a pull station on the west exit of spaces 171, 167 and the hall directly to the north. Show an additional pull station on the south side of the escalator on page 12.8. Resolved

9)      Show a correction on sheet 12.10 for forever 21 to reflect the correct construction. Resolved

10)  Show a correction on sheet 12.11 for the hall on the bottom of the page to reflect the correct construction. Resolved

11)  Show additional door and wall in hall with additional required coverage on page 12.21. Resolved

12)  Show increase candela for speaker strobe in the hall on page 12.23.Resolved

13)  On page 12.24 show additional fire door and wall on lower right side of page. Show what system the existing pull station is going to activate and any additional pull stations. Show door and wall with additional strobe coverage in hall behind Cali Nails. Resolved.

 

 

Mark Warren, Systems Plan Review

Anchorage Fire Department, Fire Prevention Division

4700 Elmore Road

Anchorage Alaska 99507

907-267-4992 desk

907-720-2245 cell

warrenmj@muni.org

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter