Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1158
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3550 PROVIDENCE DR Anchorage
Location:
Work Description:

Tenant improvement to convert a meeting room to a restaurant on the mezzaine level of the new UAA Sports Arena-gjs

Status: Closed
Project Name: ALASKA AIRLINES SPORTS ARENA RESTAURANT/PUB
Review Type: Mechanical
Result: Approved
Result Date: 4/9/2014 3:00:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C14-1158

Phone: 343-8326                                                                           Date: 3/06/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Alaska Airlines Sports Arena Restaurant/Pub 

Review Number: 329035

 

1) STATUS:   3-06-14 Comments to be addressed.      4-09-14 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.     RESOLVED 4-09-14. 

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for MUA-2, the Grease Hood and the Pizza Oven to include engineers stamp and signature, for structural review on a deferred submittal basis.          RESOLVED 4-09-14.

 

4) M401            Provide details showing compliance with the requirements for 18" clearance of the Grease Duct and Grease Hood from combustible construction per IMC 506.3.6 & 507.9.  RESOLVED PER RE-SUBMITTAL RECEIVED 3-28-14.

 

5) M401            Provide a detail for Grease Exhaust Fan EF-13 similar to 8/M602 (EF12 Detail).              RESOLVED PER RE-SUBMITTAL RECEIVED 3-28-14.

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.             RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.             RESOLVED 4-09-14.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS