Permit Number: X14-1206
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: W 716 4TH AVE Anchorage
Location:
Work Description: Deferred to Struct - Mechanical seismic and wind attachments - BWP 
Status: Closed
Project Name: Change Order of Bldg App C13-2016
Review Type: Structural
Result: Correction
Result Date: 4/13/2014 1:34:30 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C13-2016

Change Order Number: X14-1206

Project Name: Legislative Information Office

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

04/13/2014 – Initial review (328728).  Comments issued.

 

1. EDGE CLEARANCE AT POST-INSTALLED ANCHOR

Refer to Detail Pg. 2 of 8.  Please clarify the edge clearance distance for the anchors embedded close to the deck opening.

Reference: IBC Section 1603.1; AMC 23.10.104.8.1

 

2. ROD COMPRESSION CAPACITY

Refer to Detail Pg 7 of 8.  Please clarify the compression capacity of the rod hangers; the details do not provide any information on the maximum unbraced compression length of suspended equipment.

Reference: IBC Section 1603.1; AISC 360 Section E3

 