Permit Number: C14-1216
Permit Type: Commercial Building Permit - Building Sign
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Install illunminated channel letters / tb
Status: Closed
Project Name: FOREVER 21
Review Type: Structural
Result: Correction
Result Date: 4/4/2014 11:21:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Structural Comments

 

Reviewed by: Wehr, Rodney E.                                                  Permit #: C14-1216

Phone: 343-7585                                                                        Date: 4/4/14

Fax: 249-7531

Email: WehrRE@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: 800 E Dimond

Review Number: 328407

____________________________________________________________________________________

 

PERMIT STATUS

4/4/14 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

1.       Provide weight of sign.

2.       The plans call out ¼”x3” lags x 4ea for each letter.  Provide type of lag to show that it is approved for use in an exterior condition. The attachment should also be applicable for wood or metal depending on substrate/backing.

3.       Indicate substrate type on plans.

4.        (No response necessary) Additional comments may be made based on the responses received.

 

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.

 