Permit Number: C14-1158
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3550 PROVIDENCE DR Anchorage
Location:
Work Description:

Tenant improvement to convert a meeting room to a restaurant on the mezzaine level of the new UAA Sports Arena-gjs

Status: Closed
Project Name: ALASKA AIRLINES SPORTS ARENA RESTAURANT/PUB
Review Type: Fire
Result: Approved
Result Date: 3/17/2014 8:19:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Changed Status to Approved 3/17/2014 - Comments resolved over the phone with Mike Carlson.  Ol of 150 to be posted at main entrance.  Exit sign to be added near 3/H.  Inspector to field verify at final.  Plans to be redlined and/or updated with other changes or conformed set.

.

____________________________

 

1st Review 3/17/2014 - Corrections Required.

.

1.  Since the layout of the exiting has changed please indicate the number and location of the required occuppant load sign.  Your calculation shows a reduction from 140 to 130.  It is assumed this is the number to be posted and that it will be at the main exit door 4005A which has moved to the former location of doors 4004/4005C.  Please acknowledge.  Plans may be redlined and revised with any subsequent resubmittal or conformed drawings.

.

2.  Since the exiting has changed and the bar obstructs door 4005B please add a directional exit sign in the area of 3/H.