Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1114
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I for Space 182; includes elec, plbg, mech / tb

Contractor will pay building permit fee (number of inspections) / tb CONTRACTOR PAID FOR 5 INSPECTIONS 4/17/2014-GJS

CONTRACTOR PAID FOR (9) ADD'L INSPECTIONS, WILL CALL BACK THIS WEEK TO PAY FOR (6) MORE

Status: Issued
Project Name: OLD NAVY
Review Type: Fire
Result: Correction
Result Date: 2/28/2014 1:01:19 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st Review 2/28/2014 - Corrections Required.  Provide a written response to comments along with revised plans.

.

1.  Provide fire extinguishers (FE) as required per IFC 906.  Show size, type, & locations on plans.  The three FE's shown on sheet C2.0 are over spaced.  The FE in the breakroom can not serve the stock are as it is not along the path of egress.

.

2.   A separate submittal, review, and sub-permit is required for the proposed fire alarm system.  This submittal may be deferred.  Will the system within the store be voice evac type as it will need to be compatible with the voice evac system that will be installed throughout the mall?  If yes then corrdinate details and address any specific design questions with the AFD Fire System Plan Reviewer Mark Warren (267-4992).

.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter