Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1114
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I for Space 182; includes elec, plbg, mech / tb

Contractor will pay building permit fee (number of inspections) / tb CONTRACTOR PAID FOR 5 INSPECTIONS 4/17/2014-GJS

CONTRACTOR PAID FOR (9) ADD'L INSPECTIONS, WILL CALL BACK THIS WEEK TO PAY FOR (6) MORE

Status: Issued
Project Name: OLD NAVY
Review Type: Architectural
Result: Correction
Result Date: 2/21/2014 3:53:27 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C14-1114

Phone: 343-8451                                                                        Date: 02/21/14

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: OLD NAVY - 800 E DIMOND BLVD

Review Number: 327200

 

1.  Status: Architectural Corrections required.  02/21/14

 

2.  The following comments (for this change order only) based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. C0-0, Code Information / A, Applicable Building Codes;  The Applicable Building Codes as listed are correct; however, there exist Local Ammendments to most of them that are available on-line at the muni.org web site under Development Services Department, Building Safety Division.  In addition, the International Existing Building Code (IEBC) 2009 should be added to the list of Applicable Building Codes.  Please verify that these Local Ammendments are included in the Applicable Building Codes review.  02/21/14

 

4.  Drawing No. C0-0, Code Information / B, Building Classification;  The Code Study correctly identifies the Building Construction Type as IIB and VA.  Since two Building Construction Types are generally not allowed in the same building, please clarify that this was previously allowed (and is grandfathered if you are performing work under the IEBC) due to the installation of a deluge system provided between grid lines 14 and 15 for the full length of the store space.  Please also indicate that the Building Construction Type is IIB from grid line 14 and lower.   Please also indicate that the Building Construction Type is VA from grid line 15 and higher.  02/21/14

 

5.  Drawing No. A1-0c, Construction Floor Plan; The Construction Floor Plan indicates that the Old Navy Store tennant space is being reduced with a new demising wall to be located at grid line 12.  Please indicate exactly what falls under the scope of this permit and what falls under the scope of  the landlord as part of a separate permit.  Note that approval of the landlord's permit would have to run concurent with this permit and a CO only issued after the work for both permits is completed.  02/21/14

 

6.  Drawing No. A4-0, Section 5, Accoustical Ceiling Tile; Please verify that MOA Building Safety Handout A.04, Suspended Ceilings Industry Standard Construction, requirements will be incorporated into the replaced Suspended Ceilings.  02/21/14

 

7.  Drawing No. A10-0, Section 8,B, Mens Toilet and Section 1,B, Womens Toilet; The Accessible Toilet Room W.C.s require Grab Bars per ICC/ANSI A117.1 sections 604.5 and 609.  Please provide the 18 inch vertical grab bar located 39 to 41 inches from the back wall and 39 to 41 inches from the floor as shown on ICC/ANSI A117.1 Fig. 604.5.1.  02/21/14

 

8.  Drawing No. General; Verify that safety glazing is provided in all required locations per IBC section 2406.3.  02/21/14

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter