Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-2055
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

TENANT IMPROVEMENT (JINNY ROSE DAY) 

REASSIGNED TO BOB PARKER 3/6/2014.

Status: Closed
Project Name: FOREVER 21
Review Type: Mechanical
Result: Approved
Result Date: 2/12/2014 3:45:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C13-2162

Phone: 343-8326                                                                            Date: 02/12/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Forever 21

Review Number: 326703

 

1) STATUS:   01-14-14 Comments to be addressed.        2-12-14 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.     RESOLVED 2-12-14. 

 

3) Provide structural and seismic calculations plus fastening details for RTU-2 and WH to include engineers stamp and signature, for structural review on a deferred submittal basis.         RESOLVED 2-12-14.

 

4) M1.1.0 & M3.1.0          According to the architectural plans most of the interior walls on the south end of the building are 1-hour assemblies. There appear to be 9 penetrations of rated walls on the first level and seven on the mezzanine level without the required fire dampers. Coordinate with the architect and clarify required fire damper locations. (IBC 716.5.2)          RESOLVED PER RESUBMITTAL RECEIVED 2-04-14.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.           RESUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.         RESOLVED 2-12-14.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter