Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1031
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Removal of (6) bays of existing steel X-bracing & replacement with (4) new bays of steel braced frame / tb
Status: Closed
Project Name: DIMOND CENTER MALL BRACED FRAME
Review Type: Structural
Result: Correction
Result Date: 2/3/2014 12:36:59 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C14-1031

Project Name: Dimond Center Mall Braced Frame

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

02/03/2014 – Initial review (326001).  Comments issued; no further review until Comment 2 is resolved.

 

GENERAL

This review is code compliance review based on the requirements of the International Existing Building Code (IEBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.

 

The following comments must be addressed before a permit may be issued.  Additional comments may be issued following review of submitted information.

 

1. SPECIAL INSPECTION PERSONNEL

Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4

 

2. OCCUPANCY CATEGORY

Refer to Sheet S0.01.  Please justify the use of Occupancy Category II.  The total occupant load of the building appears likely to greatly exceed 5,000, even using net floor area.

Reference: IBC Section 1004.1, 1604.5; IEBC Section 707.2

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter