Project: Legislative Information Office
Review Number: 325846
1) STATUS: 12-18-13 Comments to be addressed.
01/13/2014 APPROVED.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 01-13-2014.
3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for B-1 thru B-3, PB-1' RTU-1, AC-1 & 2 and DC-1 & 2 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 01-13-2014.
4) M4.03 & M4.04 Exhaust grilles for Janitor's Closet #504 & #606 have been mislocated. RESOLVED PER RE-SUBMITTAL RECEIVED 1/10/14.
5) Clarify the location of the required RTU-1 smoke detector (IMC 606). RESOLVED PER RE-SUBMITTAL RECEIVED 1/10/14.
6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. RESOLVED 01-13-2014.