Project: AVIS MODULE CONNECTION - 5000 W INTERNATIONAL AIRPORT RD
Review Number: 325643
1. Status: Full Architectural Approval. 01/02/14
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing A2.1, The full glass door to the Vestibule and adjacent window requires safety glazing per IBC section 2406.3. Verify that safety glazing is provided in all required locations per IBC section 2406.3. 01/02/14 Resolved. This comment is resolved by Redline to the plans. 01/02/14