PERMIT INFORMATION
Permit Number: C13-1836
Project Name: West High Pool
Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
10/08/2013 – Initial review (320913). Comments issued.
GENERAL
This review is code compliance review based on the requirements of the International Existing Building Code (IEBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23. This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.
The following comments must be addressed before a permit may be issued. Additional comments may be issued following review of submitted information.
1. CONCRETE EXPOSUREThe plans note concrete work adjacent to a chlorinated pool. The concrete specifications do not appear to comply with Class C2 exposure. Please clarify.
Reference: ACI 318 Section 4.2.1, 4.3.1