Permit Number: C13-2016
Permit Type: Commercial Building Permit - None BldgCombo
Address: W 716 4TH AVE Anchorage
Location:
Work Description:

17,942 SQ FT ADD'N & $7,901,250 COMM T/I / TB

9/23/2014 PAID $4800 IN PAST DUE FEES, AND $ 5200 IN FUTURE FEES-GJS

 

12/24/2014 paid $8850 for 59 inspections plus picked up change orders.BWP

Status: Closed
Project Name: LEGISLATIVE INFORMATION OFFICE
Review Type: Private Development Site Civil Review
Result: Correction
Result Date: 12/18/2013 2:18:18 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

OK for Footing & Foundation ONLY, MG 11-18-13.    Other grading work outside of the building footprint such as storm drain and final grading are not approved.  By the developer going forward with the F&F the floor elevation will be set prior to approval of a grading & drainage plan stamped by a civil engineer that may result in significant increased costs to the developer to resolve site specific challenges to preparing an approvable site grading & drainage plan.

 

Correction, MG 11-18-13, 12-18-13.

 

1.  Ref. C3.00, Please provide details for the trench drain connection to a storm drain facility on the civil plan sheets.  If the intention is direct drainage to the sewer, please provide a non-objection letter or an approved permit from AWWU.  Not Resolved, MG 12-18-13.

 

2.  Please provide an alley section detail per M.A.S.S. detail #20-5 in addition to what is shown on Sheet C3.02.  Resolved, MG 12-18-13.

 

3.  Ref. C2.00,  Please verify that the new building roof drainage is directed internally to the existing building roof drainage.  Ref. C3.02 (existing roof drain connection note); The Engineer shall certify that the existing storm drain facility has sufficient capacity and is in sufficient condition for the proposed project.  Not Resolved, MG 12-18-13.

 

4.  PD comments may be incomplete pending further submittals.