Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1995
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: TENANT IMPROVEMENT: ADD BAR, DINING SEATING AND DISH WASHER ROOM TO EXISTING RESAURANT AT NORTON SOUND SEAFOOD. CHANGE OF USE FROM A-3 TO A-2 (907SF) - TC
Status: Closed
Project Name: NORTON SOUND RESTAURANT
Review Type: Electrical
Result: Approved
Result Date: 11/13/2013 9:20:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: C13-1995

Phone: 343-8333                                                                        Date: 10/28/2013

Fax:     249-7775

Email:  AbuobaidDH@muni.org

Permit  Manager: Tommy Cornell   

Phone: 343-8181

Email:  CornellTH@muni.org

Project: Norton Sound Seafood Rest (Fax: no fax)

___________________________________________________________________________________

2/5/2015

The electrical comments are addressed by the engineer in his letter. approved

@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@

 

1.  The following comments based on the 2011 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           

2.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION ON FLOOR PLAN & PANEL SCHEDULS:

Sheet E3 (Floor Plan and Panel Schedules Circuit Identifications). Panel and floor plan do not have same circuit identifications. For examples: circuits on the floor plans are identified by numbers such as 209, 802, 211 etc. These circuit have matched identifications on floor plans and panels schedule. Refer to NEC 408.4 for circuit identifications.

 

3.  EXISTING SERVICE LOAD CALCULATIONS:
Sheet E3. The plans have no calculations for feeder loads for the existing building as required by NEC Section 220.87. Please address.

 

4.  PANEL 113NPB LOAD CALCULATIONS:
Sheet E3. The panel schedule is missing the load for all the existing circuit. Please provide all the exiting circuits load and show by calculations that the panel can carry the added load. Refer to NEC Section 220.87. Please address.

 

5.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS