Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1886
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I includes elec,plbg,mech / tb 

**Master fill/grade C13-1529; Core & Shell C13-1660**

Status: Closed
Project Name: CHILI'S
Review Type: Mechanical
Result: Correction
Result Date: 11/5/2013 3:56:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1886

Phone: 343-8326                                                                           Date: 11/05/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Chili's

Review Number: 323477

 

1) STATUS:   11-5-13 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for RTU-3, MAU-1, Kitchen Hoods 1-4 and the domestic water expansion tank to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) 01 & 05/M202          A smooth, cleanable, nonabsorbent and noncombustible material is to be installed between the hood and the hood and the gypsum or cementatious wallboard over an area extending not less than 18 inches in all directions from the hood and at least below the level of the cooking surface. (Exception to IMC 507.9) Provide clarification.

 

5) M101          Note #11 should reference detail #10 on M201.

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.             RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

  

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter