Project: CRC Health Group
Review Number: 3322825
1) STATUS: 10-23-13 Comments to be addressed.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) The engineer of record's signature and date are missing from the drawings.
4) 3/M2 It appears that the domestic cold water is being supplied from a connection at the existing bathrooms with a 3/4" line (ref. note #3). Please clarify the CW line increase to 1-1/2" above Privacy Room #122 which then reduces to 3/4" before the end of line connections to P-5 and P-4.
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.