Permit Number: C13-1991
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 121 FIREWEED LN Anchorage
Location:
Work Description: TENANT IMIPROVEMENT (JINNY ROSE DAY)
Status: Closed
Project Name: CRC HEALTH GROUP
Review Type: Fire
Result: Approved
Result Date: 10/25/2013 3:28:48 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Approved 10/25/2013 per plans with following notes.  Per code study this is not an aambulatory health care facility.

.

1.  Add or relocate a fire extinguisher @ 3/C as shown on A2.1 to meet 75 ft travel distance.  Inspector will field verify.

.

2.  Exit signs may be deleted at corner corridor 1.5/B & F.  Exit signs at doors 100B & C are sufficient for common path and clarity.

.

3.  Provide emergency lighting at exterior discharge of both exits.  Inspector will field verify.