Approved 10/25/2013 per plans with following notes. Per code study this is not an aambulatory health care facility.
.
1. Add or relocate a fire extinguisher @ 3/C as shown on A2.1 to meet 75 ft travel distance. Inspector will field verify.
2. Exit signs may be deleted at corner corridor 1.5/B & F. Exit signs at doors 100B & C are sufficient for common path and clarity.
3. Provide emergency lighting at exterior discharge of both exits. Inspector will field verify.