Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1941
Permit Type: Commercial Building Permit - None BldgNew
Address: 3350 OLD INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:

384SF OCC. "S-2" - TC

Status: Closed
Project Name: AVIONICS STORAGE BUILDING
Review Type: Architectural
Result: Correction
Result Date: 10/8/2013 11:15:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                         Permit #: C13-1941

Phone: 343-8326                                                                         Date: 10/08/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Avionics Storage Building

Review Number: 322082

 

1) STATUS:   10-08-13 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) A/A-1         The continuous 12" X 12" timber skid is required to be treated lumber. Please clarify.

 

4) A-1             A full size landing is required at the top of the stairs. (IBC 1008.1.5)

 

5) A-1             Handrails with extensions are required on both sides of the stairs.

(IBC1009.12 & 1012)

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 

 

 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS