Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1939
Permit Type: Commercial Building Permit - None BldgAlter
Address: 700 G ST Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO THE 13TH FLOOR DEMO INTERIOR WALLS AND CEILINGS AND INSTALL NEW CEILING, FLOORING AND WALLS (JINNY ROSE DAY)
Status: Issued
Project Name: CONOCO PHILLIPS 13TH FLOOR
Review Type: Fire
Result: Correction
Result Date: 10/14/2013 9:17:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st Review 10/14/2013 - Corrections Required.  Clarify scope of work.  see comments below.

.

1.  Verify that the elevator lobby is not within the scope of work and that you are maintaining the required lobby separation.  It is not clear if your intent is to demo these doors as you are showing them as dashed lines.

.

2.  Sheet G0.2 references a fire rated exit corridor.  If the intent is to maintain this rating then doors 1300A & B are required to be rated.  Please show rating on the door schedule.

.

3.  Doors 1300A & B appears to alter the natural path of egress.  Verify or adjust exit signage accordingly.  IE: The path from the N/E corner directs occupants to the same stair rather than to both stairs.  The path from the S/W corner appears to do the same.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS