Comm T/I: cosmetic renovation of finishes on 4th floor; ceiling grid, flooring, wall finishes; includes elec, plbg, mech / tb
7/17/2015 paid for (10) inspections
Reviewed by: Crafts, Donald E. Permit #: C13-1821
Phone: 343-8451 Date: 09/23/13, 10/01/13
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierT@muni.org
Project: ALASKA REGIONAL 4TH FLOOR - 2801 DEBARR RD
Review Number: 321862
1. Status: Architectural Corrections required. 09/23/13 Status: Full Architectural Approval. 10/01/13
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. Cover, Plan Review Data , Governing State and Local Codes; Revise: National Electric Code (NEC) 2008 Edition to National Electric Code (NEC) 2011 Edition. 9/23/13 Resolved. Revised to National Electric Code (NEC) 2011 Edition. 10/01/13
4. Drawing No. Cover, Wall Symbols, Non-Rated Partition to Deck; Provide deflection tracking at the top of the new Non-Rated Partitions to Deck (at the underside of the roof structural members) per IBC Section 1604. 9/23/13 Resolved. Comment rescinded, since detail is provided in a separate plan set, Drawing A4.51, Detail 1. 09/23/13
5. Drawing No. Cover, Wall Symbols, Smoke Partition to Deck; Provide deflection tracking at the top of the new Smoke Partitions and all other rated partitions and barriers to Deck (at the underside of the roof structural members) per IBC Section 1604. 9/23/13 Resolved. Comment rescinded, since detail is provided in a separate plan set, Drawing A4.51, Details 3, 4, 7, 11, 12, etc. 09/23/13
6. Drawing No. A2.1F and A2.2F, Fourth Floor Enlarged Plans; Where is the legend for the numbers in the hexagons shown on these details? Please Provide. 9/23/13 Resolved. Shown on Drawing No. A2.00. 10/01/13
7. Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes; Where is the legend for the numbers shown on the door schedule for hardware? All other data is provided on the same drawing. Please Provide door hardware details. Verify that all new doors shall be readily openable from the egress side without the use of a key or special knowledge per IBC Sec. 1008.1.9. 9/23/13 Resolved. The Specifications were submitted. 10/01/13
8. Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes; No Door Hardware Schedule is provided with the plans. Several Egress Doors are doors with card readers. Verify that these Doors comply with all the requirements of IBC Section 1008.1.4.4, as applicable. 9/23/13 Resolved. The Specifications were submitted. 10/01/13
9. Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes and A1.04B, Fourth Floor Part B Noted and Dimensioned Plan; Door 4308 is identified as having a 45 minute fire-resistance rating; however, the door appears to be located in a 2 hour and smoke barrier wall. Thus, Door 4308 should be identified as having a 90 minute fire-resistance rating per IBC Table 715.4. Please verify. 9/23/13 Resolved. Revised to having a 90 minute fire-resistance rating per IBC Table 715.4. 10/01/13
10. Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes and A1.04B, Fourth Floor Part B Noted and Dimensioned Plan; Doors 4201, 4202B, 4302A, 4302B, are identified as being provided with Magnetic Hold-Open Devices; however, the door schedule does not identify these doors as being provided with smoke seals. Please verify if smoke seals are provided. 9/23/13 Resolved. The Specifications were submitted. 10/01/13
11. Drawing No. F1.04B, Fourth Floor Part B Finish Plan; Where is the legend for the numbers shown on the plan for finish material? Please Provide. 9/23/13 Resolved. Comment rescinded, since legend is provided in a separate plan set, Drawing A0.01. 09/23/13