Permit Number: X13-1903
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 3645 AIRCRAFT DR Anchorage
Location:
Work Description: Change 1-1/2" gas line to 1"; change 1-1/2" water line to 1"; add in-floor heating with boiler / tb
Status: Closed
Project Name: Change Order of Bldg App 06 5269
Review Type: Plumbing
Result: Approved
Result Date: 9/30/2013 3:44:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: 06-5269; X12-1903

Phone: 343-8451                                                                        Date: 09/27/13, 09/30/13

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: RATCLIFF DEVELOPMENT Lake Hood Hanger - 3635 AIRCRAFT DR

Review Number: 321739

 

1.  Status: Plumbing Corrections required.  09/27/13    Please Provide Complete Plumbing and Gas line size calculations for review.  09/27/13   Status: Full Plumbing Approval.  09/30/13

 

2.  The following comments based on the 2003 Uniform Plumbing Code (UPC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the UPC or any federal, state, or local regulations.

 

3.  Please Provide Complete Plumbing and Gas line size calculations for review for the rivised lines sizes in this change order.  09/27/13   RESOLVED. Line size justification was provided.  09/30/13

 

4.  This permit was origninally for two hangers on the property.  This change order is for the second hanger revisions to be consistent with the first hanger.  The project was permitted under the 2003 code series.  10/02/13