Tenant improvement-gjs
PERMIT REASSIGNED TO TOMMY-GJS
1st Review 9/27/2013 - Corrections Required.
.
1. Provide electrical plans showing locations of emergency light and exit sign fixtures whether existing or new. This submittal may be deferred.
2. Provide fire extinguishers (FE's) as required per IFC 906. Travel distance from any point on the floor shall be within 75 ft travel. FE's shall be along the path of egress (near exit stairs). Add or redistribute as required as travel distance is exceeded in some areas.
3. The egress width at the aisle between 2 & 3/C is too narrow due to the columns. Per IBC 1017.2 the minimum required width is 36 inches.