Permit Number: C13-1821
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Comm T/I: cosmetic renovation of finishes on 4th floor; ceiling grid, flooring, wall finishes; includes elec, plbg, mech / tb

7/17/2015 paid for (10) inspections

Status: Closed
Project Name: ALASKA REGIONAL 4TH FLOOR UPGRADES
Review Type: Architectural
Result: Correction
Result Date: 9/23/2013 4:38:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C13-1821

Phone: 343-8451                                                                        Date: 09/23/13

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: ALASKA REGIONAL 4TH FLOOR - 2801 DEBARR RD

Review Number: 320586

 

1.  Status: Architectural Corrections required.  09/23/13

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. Cover, Plan Review Data , Governing State and Local Codes; Revise: National Electric Code (NEC) 2008 Edition to National Electric Code (NEC) 2011 Edition.  9/23/13

 

4.  Drawing No. Cover, Wall Symbols, Non-Rated Partition to Deck; Provide deflection tracking at the top of the new Non-Rated Partitions to Deck (at the underside of the roof structural members) per IBC Section 1604.  9/23/13    Resolved.  Comment rescinded, since detail is provided in a separate plan set, Drawing A4.51, Detail 1.  09/23/13

 

5.  Drawing No. Cover, Wall Symbols, Smoke Partition to Deck; Provide deflection tracking at the top of the new Smoke Partitions and all other rated partitions and barriers to Deck (at the underside of the roof structural members) per IBC Section 1604.  9/23/13    Resolved.  Comment rescinded, since detail is provided in a separate plan set, Drawing A4.51, Details 3, 4, 7, 11, 12, etc.  09/23/13

 

6.  Drawing No. A2.1F and A2.2F, Fourth Floor Enlarged Plans; Where is the legend for the numbers in the hexagons shown on these details?  Please Provide.  9/23/13

 

7.  Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes; Where is the legend for the numbers shown on the door schedule for hardware?  All other data is provided on the same drawing.  Please Provide door hardware details.  Verify that all new doors shall be readily openable from the egress side without the use of a key or special knowledge per IBC Sec. 1008.1.9.  9/23/13

 

8.  Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes; No Door Hardware Schedule is provided with the plans.  Several Egress Doors are doors with card readers.  Verify that these Doors comply with all the requirements of IBC Section 1008.1.4.4, as applicable.  9/23/13

 

9.  Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes and A1.04B, Fourth Floor Part B Noted and Dimensioned Plan; Door 4308 is identified as having a 45 minute fire-resistance rating; however, the door appears to be located in a 2 hour and smoke barrier wall.  Thus, Door 4308 should be identified as having a 90 minute fire-resistance rating per IBC Table 715.4. Please verify.  9/23/13

 

10.  Drawing No. A6.01F, Door Schedule - Fourth Floor Finishes and A1.04B, Fourth Floor Part B Noted and Dimensioned Plan; Doors 4201, 4202B, 4302A, 4302B, are identified as being provided with Magnetic Hold-Open Devices; however, the door schedule does not identify these doors as being provided with smoke seals.  Please verify if smoke seals are provided.  9/23/13

 

11.  Drawing No. F1.04B, Fourth Floor Part B Finish Plan; Where is the legend for the numbers shown on the plan for finish material?  Please Provide.  9/23/13    Resolved.  Comment rescinded, since legend is provided in a separate plan set, Drawing A0.01.  09/23/13