228 Sq Ft vault for strom water pump - BWP **Changed to expedited 8/28/2013.BWP**
Arctic Electric Inc. paid for 3 inspections on E13-1571.
PERMIT INFORMATION
Permit Number: C13-1779
Project Name: Pump Station K Vault
Permit Manager: Bob Parker | ph: (907) 343-8391 | parkerrw@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
09/04/2013 – Initial review (320100). Comments issued.
GENERAL
This review is code compliance review based on the requirements of the International Building Code (IBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23. This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.
The following comments must be addressed before a permit may be issued. Additional comments may be issued following review of submitted information.
1. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4