Reviewed by: Bolen, Wayne A. Permit #: C13-1646
Phone: 343-8072 Date: 8/14/12013
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska USA Federal Credit Union Chiller
Review Number: 318671
____________________________________________________________________________________
PERMIT STATUS
8/14/2013 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please provide the attachment of the chillers to the frames. Reference AAC section 23.10.104.8.
2. Please verify the stresses in the existing roof framing has not been increased by more than 10%. Where any of the stresses have been increased by more than 10% these elements must be checked to the current code level load requirements. Reference IEBC section 303.3.