Permit Number: C13-1660
Permit Type: Commercial Building Permit - None BldgAdd
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

7,664 SQ FT ADDITION; 20% deduction for core & shell / tb

**master fill/grade C13-1529** 

Status: Closed
Project Name: DIMOND CENTER WEST MALL ADDITION
Review Type: Mechanical
Result: Approved
Result Date: 8/13/2013 4:55:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1660

Phone: 343-8326                                                                          Date: 8/13/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: iDimond Center West Mall Addition

Review Number: 318640

 

1) STATUS:   7-25-13 Comments to be addressed.        8-13-13 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.     RESOLVED 8-13-13. 

 

3) Provide structural, seismic and wind load calculations plus fastening details for RTU-1 thru 5 to include engineers stamp and signature, for structural review on a deferred submittal basis.         RESOLVED 8-13-13.

 

4) Provide 100% mechanical drawings so that a complete review may be accomplished.       RESOLVED PER RESUBMITTAL RECEIVED 8-02-13.

 

5) Provide total CFM and minimum outside air setting (IMC 403) required for each of the rooftop units RTU-1 thru 5.             RESOLVED PER RESUBMITTAL RECEIVED 8-02-13.

 

 

 

 