Reviewed by: Crafts, Donald E. Permit #: C13-1691
Phone: 343-8451 Date: 08/21/13
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: CRITERION GENERAL, INC.- 4000 CREDIT UNION DR - Alaska USA
Review Number: 317910
1. Status: Full Architectural Approval. 08/21/13
2. The following comments (for this change order only) based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing A-1, Plan; The Elevator Lobby indicates a one-hour fire-resistive barrier on one end and nothing is indicated on the other. Please Clarify. 08/21/13 RESOLVED. An existing pair of 45 minute fire-resistive doors on hold open are located on the other end of the lobby. 08/21/13