Click Here To Go Back To Permit Information

Permit Number: C13-1660
Permit Type: Commercial Building Permit - None BldgAdd
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

7,664 SQ FT ADDITION; 20% deduction for core & shell / tb

**master fill/grade C13-1529** 

Status: Closed
Project Name: DIMOND CENTER WEST MALL ADDITION
Review Type: Mechanical
Result: Correction
Result Date: 7/25/2013 2:26:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1660

Phone: 343-8326                                                                          Date: 7/25/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: iDimond Center West Mall Addition

Review Number: 317860

 

1) STATUS:   7-25-13 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations plus fastening details for RTU-1 thru 5 to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) Provide 100% mechanical drawings so that a complete review may be accomplished.

 

5) Provide total CFM and minimum outside air setting (IMC 403) required for each of the rooftop units RTU-1 thru 5.

 

 

 

 