Permit Number: C13-1177
Permit Type: Commercial Building Permit - None BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb

2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections

Status: Closed
Project Name: ALASKA REGIONAL RENOVATIONS & ELECTRICAL ADDITIONS
Review Type: Storm Water
Result: Correction
Result Date: 6/25/2013 10:48:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1.  Complete AG 21 Checklist 2 and 3. Provide all documentation required by the checklists. Comment by S.Ellis 4/2/13. Checklist 2 and 3 Provided, but required  documents needed for the project on checklist # 2  need to be submitted.6/25/13 PL.

2. Provide Storm water Pollution Prevention Plan Type 2 SWPPP

3.  Please submit a Permanent Storm water Quality Control Plan - See Section 7, STORM  WATER TREATMENT PLAN REVIEW Guidance Manual Third Edition :http://www.muni.org/Departments/works/project_management/Documents/SWTPRGM%20Sept2010.pdf

4.Please submit a Permanent Maintenance and Operations Plan- See Section 8, STORM WATER     TREATMENT PLAN REVIEW Guidance Manual Third Edition: the Plan shall provide more specific guidance for inspection of the permanent BMPs, Provide periodic inspection of the parking lot for spills and debris. The parking lot is required to be swept twice per year, By June 15th and Oct 15th. Permanent BMPs are required to be cleaned on the same schedule. http://www.muni.org/Departments/works/project_management/Documents/SWTPRGM%20Sept2010.pdf

Note: On comment #4, a maintenance plan for the parking lot was submitted. but on plan sheet  it show a fuel storage tank.Please provide a maintenance and opreation plan for the fuel storage tank.