NEW INTERIOR BUILD OUT OF A STARBUCKS CAFE SPACE. INCLUDES PLUM, MECH, AND ELEC. NO CHANGE TO EXISTING BULIDING EXITS FOR SPACE D24 - TC
PERMIT READY TO CLOSE- JUST NEED TO PAY $300 INSPECTION FEE-GJS
PLANS ARE ALREADY ARCHIEVED.
Reviewed by: Bergstrom, Leigh W. Permit #: C13-1458
Phone: 343-8326 Date: 7/01/2013
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: CornellTA@muni.org
Project: Starbucks 5TH AVE
Review Number: 315928
1) STATUS: 6-05-13 Comments to be addressed. 7-01-13 APPROVED.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 7-01-13.
3) Provide structural and seismic calculations plus fastening details for WSHP-1 and the water heater to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 7-01-13.
4) P-001 Provide size and performance data for the water heater and expansion tank. This will be a requirement for the health department. RESOLVED PER RESUBMITTAL RECEIVED 6-24-13.
5) P-112 The 3-compartment sink is required to have a direct connection to the sanitary system with the adjacent floor sink flush mounted.(UPC 704.3 plus local amendment) RESOLVED PER RESUBMITTAL RECEIVED 6-24-13.
6) 8/P-501 The domestic water supplied to the water softener and filters requires backflow protection per UPC 603 and the AWWA Cross-Connection Control Manual. RESOLVED PER RESUBMITTAL RECEIVED 6-24-13.
7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. RESOLVED 7-1-13.