Permit Number: X13-1465
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 530 BENSON BLVD Anchorage
Location:
Work Description: DEFERRED SUBMITTAL:  GLASS BLOCK STRUCTURAL ATTACHMENT
Status: Closed
Project Name: Change Order of Bldg App C13-1372
Review Type: Structural
Result: Correction
Result Date: 7/15/2013 1:43:15 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C13-1372

Change Order Number: X13-1465

Project Name: 530 W Benson Vestibule

Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

07/15/2013 – Initial review (315414).  Comments issued.

 

1. HEADER AT STOREFRONT

The plans note a 1/2 in. x 2 in. flat bar spanning the width of the opening (12 ft.). No calculations were provided showing the adequacy of the bar supporting the out-of-plane wind loads of the storefront below plus the tributary wind loads from the glass block above.  It does not appear the bar will be sufficient for both flexure and deflection.  Please clarify design.

Reference: IBC Section 1604.3.1, 1604.4; AISC 360 Section F2.1

 