Permit Number: C13-1547
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1553 GAMBELL ST Anchorage
Location:
Work Description: Placement of 12 antenna & associated equipment on an existing tower / tb
Status: Closed
Project Name: CHESTER CREEK RELO AN2349
Review Type: Architectural
Result: Approved
Result Date: 6/20/2013 12:22:44 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Crafts, Donald E.                                                  Permit #: C13-1547

Phone: 343-8451                                                                        Date: 06/20/13

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: CHESTER CREEK RELO AN2349 - 1553 GAMBELL ST

Review Number: 315314  

 

1.  Status: Full Architectural Approval.  06/20/13

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. A-7, Stair Section,  Verify that the west exit landing and stair portions higher than 30 inches are provided with a 42 inch high Guard per IBC Section 1013.  Note that this is shown on the landing; however, it is not shown on the highest stair (higher than 30 inches).  06/19/13