Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb
2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections
Reviewed by: Bergstrom, Leigh W. Permit #: C13-1177
Phone: 343-8326 Date: 6/12/2013
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska Regional Renovations
Review Number: 314754
1) STATUS: 4-12-13 Comments to be addressed. 6-12-13 APPROVED.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 6-12-13.
3) P2.07 The lavatories P-5 and P-23 in the two public bathrooms opposite elevator #1 require mixing valves per UPC 413.1. RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.
4) P2.07 BV-5 above Nurse Station 7-MS134 should be located on the 3/4" HWR branch coming from the NW corner. RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.
5) P2.07 The pipe labeled as 2" CW coming from the shaft just south of elevator #5 should be labeled as 2" HW. RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.
6) P0.01 Clarify the abbreviations G.N. and W.B. missing from the plumbing abbreviations. RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.
7) P0.01 Seismic straps are missing from the water heater details required per IBC 508.2. RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.
8) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RESOLVED 6-12-13.