Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1177
Permit Type: Commercial Building Permit - None BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb

2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections

Status: Closed
Project Name: ALASKA REGIONAL RENOVATIONS & ELECTRICAL ADDITIONS
Review Type: Mechanical
Result: Approved
Result Date: 6/12/2013 11:21:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1177

Phone: 343-8326                                                                          Date: 6/12/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Alaska Regional Renovations

Review Number: 314753

 

1) STATUS:   4-12-13 Comments to be addressed.     6-12-13 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.   RESOLVED 6-12-13. 

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for AC-EL1, B-4, AHU-9 & 10, GT H1 thru 5 Day Tank, IEF-10-1, MVP-2, Deaerator, Condensate Receivers and the Underground Fuel Storage Tank to include engineers stamp and signature, for structural review on a deferred submittal basis.      RESOLVED 6-12-13.

 

4) M1.01         Please clarify VF-EL5. It did not appear to be on the equipment schedule.         RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.

 

5) M3.02         The plan view of  Mechanical Room 8-ME8002 is missing a FSD at the shaft penetration. (IBC 716.5.3)               RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.

 

6) M3.02         Please clarify the required FSD on the shaft penetration of the supply air ducts which cannot be seen on these plan views. (IBC 716.5.3)     RESOLVED PER RESUBMITTAL RECEIVED 6-04-13.

 

7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.               RESOLVED 6-12-13.

 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS