Permit Number: C13-1177
Permit Type: Commercial Building Permit - None BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb

2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections

Status: Closed
Project Name: ALASKA REGIONAL RENOVATIONS & ELECTRICAL ADDITIONS
Review Type: Architectural
Result: Approved
Result Date: 6/13/2013 2:59:10 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C13-1177

Phone: 343-8451                                                                        Date: 04/25/13, 06/13/13

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: ALASKA REGIONAL RENOVATIONS & - 2801 DEBARR RD

Review Number: 314751

 

1.  Status: Architectural Corrections required.  04/25/13   Status: Full Architectural Approval.  06/13/13

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing A1.07A, Seventh Floor Noted and Dimentional Plan and Drawing A6.01, Door Schedule; Door 7135 is shown located in a one hour fire resistive fire barrier on Drawing A1.07A.  Door 7135 is shown as not rated on Drawing A6.01.  It appears that this door should be a 45 minute fire resistive rated assembly.  04/25/13    Resolved.  The plans have been revised to add the 45 minute fire resistive rated assembly for Door 7135.  06/13/13

 

4  Drawing A(various), The existing handicap bathroom W.C.s require Grab Bars per ICC/ANSI A117.1 sections 604.5 and 609.  Please verify the presence of or provide the 18 inch vertical grab bar located 39 to 41 inches from the back wall and 39 to 41 inches from the floor as shown on ICC/ANSI A117.1 Fig. 604.5.1.  04/25/13    Resolved.  The plans have been revised to add the 18 inch vertical grab bar located 39 to 41 inches from the back wall and 39 to 41 inches from the floor as shown on ICC/ANSI A117.1 Fig. 604.5.1.  06/13/13