TENANT IMPROVEMENT (JINNY ROSE DAY)
Reviewed by: Bolen, Wayne A. Permit #: C13-1406
Phone: 343-8072 Date: 6/18/2013
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: The Rock Wood Fired Pizza & Spirits
Review Number: 314257
____________________________________________________________________________________
PERMIT STATUS (no response required) 6/18/2013: Submittal incomplete. Full review not completed.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please provide the attachment of the MAU and RTU's to the curb. "Fasteners per Manufacturer" is not accetable as the inspectors need something approved by MOA to inspect from. Reference AAC section 23.10.104.8.