PERMIT INFORMATION
Permit Number: C13-1254
Change Order Number: X13-1376
Project Name: Michael Kors
Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
06/06/2013 – Initial review (313982). Comments issued.
08/20/2013 - Reviewed responses (313982). OK for structural.
1. STATEMENT OF SPECIAL INSPECTIONS
Please provide a detailed statement of special inspections in accordance with IBC Chapter 17. This may be provided on the plans or as a separate document.
Reference: IBC Section 1705.2
8/20/13 - Resolved. Redlined on plans. MMP
2. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4
8/20/13 - Resolved. Letter provided by special inspection firm. MMP