Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1458
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

NEW INTERIOR BUILD OUT OF A STARBUCKS CAFE SPACE. INCLUDES PLUM, MECH, AND ELEC. NO CHANGE TO EXISTING BULIDING EXITS FOR SPACE D24 - TC

PERMIT READY TO CLOSE- JUST NEED TO PAY $300 INSPECTION FEE-GJS

PLANS ARE ALREADY ARCHIEVED.

Status: Closed
Project Name: STARBUCKS 5TH AVE
Review Type: Plumbing
Result: Correction
Result Date: 6/5/2013 12:30:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1458

Phone: 343-8326                                                                          Date: 6/05/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Starbucks 5TH AVE

Review Number: 313822

 

1) STATUS:   6-05-13 Comments to be addressed.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) Provide structural and seismic calculations plus fastening details for WSHP-1 and the water heater to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) P-001           Provide size and performance data for the water heater and expansion tank. This will be a requirement for the health department.

 

5) P-112           The 3-compartment sink is required to have a direct connection to the sanitary system with the adjacent floor sink flush mounted.(UPC 704.3 plus local amendment)

 

6) 8/P-501        The domestic water supplied to the water softener and filters requires backflow protection per UPC 603 and the AWWA Cross-Connection Control Manual.

 

7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.                                   RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 

 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS