NEW INTERIOR BUILD OUT OF A STARBUCKS CAFE SPACE. INCLUDES PLUM, MECH, AND ELEC. NO CHANGE TO EXISTING BULIDING EXITS FOR SPACE D24 - TC
PERMIT READY TO CLOSE- JUST NEED TO PAY $300 INSPECTION FEE-GJS
PLANS ARE ALREADY ARCHIEVED.
Reviewed by: Crafts, Donald E. Permit #: C13-1458
Phone: 343-8451 Date: 05/28/13
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: STARBUCKS 5TH AVE - 320 W 5TH AVE
Review Number: 313818
1. Status: Architectural Corrections required. 05/28/13
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing G0001, Code Notes; The Type of Construction is indicated to be II-A. The Type of Construction for the 5th Avenue Mall should be indicated to be I-A. 05/28/13 Resolved. This comment is resolved by Redline to the plans. 05/28/13
4. Drawing G0001, Code Notes; Revise: National Electric Code (NEC) 2008 Edition to National Electric Code (NEC) 2011 Edition. 05/28/13 Resolved. This comment is resolved by Redline to the plans. 05/28/13