Permit Number: C13-1252
Permit Type: Commercial Building Permit - Regular FillGrade
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 25,000 cyds fill, 30,000 cyd excavation, 55,000 cyds grading rehabilitate athletic areas- constructing 10-lane track & two artificial turf fields / tb
Status: Issued
Project Name: FILL/GRADE WEST HIGH SCHOOL
Review Type: Structural
Result: Approved
Result Date: 5/28/2013 11:06:59 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by:    Ron Wilde                                                                    Permit #: C13-1252

Phone:              343-8371                                                                     Date:    4-24-2013

Fax:                  343-8200

Email:               wilderg@muni.org

 

Permit Tech:     Tony Barganier

Phone:              343-8339

Email:               barganierta@muni.org

Project:            West High track – Fill and Grade

 

1.  PERMIT STATUS

4-24-2013 – Permit reviewed. Comments issued.

 

2.  Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AMC 23.10), Grading, Excavation and Fill code (AMC 23.105), and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

3.  GRADING LABELS

The drawings refer to “Grading B and D-1,” and “Select material, Type A.”  These terms need to be defined on the drawings or you can use the soil designations used in the Municipality of Anchorage Standard Specifications (MASS) which are more familiar to contractors in the Anchorage area.  It is not sufficient for gradation information to be shown only in the specifications.  All information showing how to construct the project needs to be on the drawings.  Note: The similar grading project for East High School used the MASS soil type designations.

 

4.  SPECIAL INSPECTION AND STATEMENT OF SPECIAL INSPECTION

Please provide a Statement of Special Inspection showing the special inspector’s responsibilities as per AMC 23.105.115.4, IBC 1704.7, and IBC Table 1704.7.

 

If you have any questions please call me, Ron Wilde, at 343-8371.

 

5.  LETTER INDICATING WHO IS HIRING THE SPECIAL INPECTOR

Please provide an email, or letter stating who is hiring the special inspector and what his relationship is to the project.  See IBC, 1704.1, paragraph 1.

 

6.  SPECIAL INSPECTION AND TESTING AGREEMENT

Please fill out and submit a signed copy of the Special Inspection and Testing Agreement.  This agreement can be found beginning on page 7 of the Special Inspection Program Requirements http://www.muni.org/Departments/OCPD/development/BSD/BSDDocuments/SpecialInspectionGuidelines.pdf