Approved 4/08/2013 per phone call to Eric Cowling. Note that all EM fixtures are battery type. Agreed EM's technically not required in elevator lobby & corridor due to meeting common path but agrees this is a gray area and makes sense. He will add EM's to both areas. Also will add a directional exit sign at S/E corner of floor directing to east stair 318.
__________________________
1st Review 4/05/2013 @ counter - Corrections Required - OK to issue permit except for elcetrical.
.
1. Elevator Lobby 300 and corridor 301 requires emergency lighting.
2. The directional exit sign by elecrtrical room 304 may not be obvious to the intended egress route. The south/east corner of the floor near room 323 may also require an additional perpindicular directional sign to direct occupants to stair 303.