Reviewed by: Ron Wilde Permit #: C13-1252
Phone: 343-8371 Date: 4-24-2013
Fax: 343-8200
Email: wilderg@muni.org
Permit Tech: Tony Barganier
Phone: 343-8339
Email: barganierta@muni.org
Project: West High track – Fill and Grade
1. PERMIT STATUS
4-24-2013 – Permit reviewed. Comments issued.
2. Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AMC 23.10), Grading, Excavation and Fill code (AMC 23.105), and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
3. GRADING LABELS
The drawings refer to “Grading B and D-1,” and “Select material, Type A.” These terms need to be defined on the drawings or you can use the soil designations used in the Municipality of Anchorage Standard Specifications (MASS) which are more familiar to contractors in the Anchorage area. It is not sufficient for gradation information to be shown only in the specifications. All information showing how to construct the project needs to be on the drawings. Note: The similar grading project for East High School used the MASS soil type designations.
4. SPECIAL INSPECTION AND STATEMENT OF SPECIAL INSPECTION
Please provide a Statement of Special Inspection showing the special inspector’s responsibilities as per AMC 23.105.115.4, IBC 1704.7, and IBC Table 1704.7.
If you have any questions please call me, Ron Wilde, at 343-8371.
5. LETTER INDICATING WHO IS HIRING THE SPECIAL INPECTOR
Please provide an email, or letter stating who is hiring the special inspector and what his relationship is to the project. See IBC, 1704.1, paragraph 1.
6. SPECIAL INSPECTION AND TESTING AGREEMENT
Please fill out and submit a signed copy of the Special Inspection and Testing Agreement. This agreement can be found beginning on page 7 of the Special Inspection Program Requirements http://www.muni.org/Departments/OCPD/development/BSD/BSDDocuments/SpecialInspectionGuidelines.pdf