Reviewed by: Bergstrom, Leigh W. Permit #: C13-1202
Phone: 343-8326 Date: 3/27/2013
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: West High School Dressing Rooms
Review Number: 310630
1) STATUS: 3-27-13 Comments to be addressed.
2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.
3) G1.2 Code Analysis Provide the building construction type per IBC 602.
4) A2.9 If the building is Type I or Type II construction, the 2X4's must be fire retardant treated per IBC 603.1.25.1. Please clarify.