Reviewed by: Bolen, Wayne A. Permit #: C12-1324
Phone: 343-8072 Date: 4/2/2013
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Sam’s Club Mechanical and Electrical Equipment Seismic Restraint
Review Number: 310572
____________________________________________________________________________________
PERMIT STATUS
4/2/2013 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please have the engineer of record for the restraint of the mechanical and electrical equipment stamp and sign each page that is to be used for construction as required by the Alaska State Statutes section 08.48.221.
2. RTU 1, 5, 8, 13, 14, 15, 16, 17, 20, AND 24
Reference DWG. NO. 208 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.
3. RTU 4, 7, 9, 10, 12, 18, 22, AND 23
Reference DWG. NO. 209 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.
4. RTU 2, 3, 6, 11, 19, AND 21
Reference DWG. NO. 210 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.
5. AHU-1
Reference DWG. NO. 211 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.