Permit Number: X13-1201
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: N 1074 MULDOON RD Anchorage
Location:
Work Description: DEFERRED SUB:  Seismic protection data for HVAC, Mechanical, Electrical / tb
Status: Closed
Project Name: Change Order of Bldg App C12-1324
Review Type: Structural
Result: Approved
Result Date: 4/2/2013 10:50:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C12-1324

Phone: 343-8072                                                                        Date: 4/2/2013

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Sam’s Club Mechanical and Electrical Equipment Seismic Restraint

Review Number: 310572

____________________________________________________________________________________

 

PERMIT STATUS

4/2/2013 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

1. Please have the engineer of record for the restraint of the mechanical and electrical equipment stamp and sign each page that is to be used for construction as required by the Alaska State Statutes section 08.48.221.

 

2. RTU 1, 5, 8, 13, 14, 15, 16, 17, 20, AND 24

Reference DWG. NO. 208 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.

 

3. RTU 4, 7, 9, 10, 12, 18, 22, AND 23

Reference DWG. NO. 209 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.

 

4. RTU 2, 3, 6, 11, 19, AND 21

Reference DWG. NO. 210 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.

 

5. AHU-1

Reference DWG. NO. 211 of the calculations. The detail at the bottom of the page indicates the attachment of the curb to the roof as "by others." Please provide this attachment.