Permit Number: C13-1177
Permit Type: Commercial Building Permit - None BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb

2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections

Status: Closed
Project Name: ALASKA REGIONAL RENOVATIONS & ELECTRICAL ADDITIONS
Review Type: Plumbing
Result: Correction
Result Date: 4/12/2013 10:17:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C13-1177

Phone: 343-8326                                                                          Date: 4/12/2013

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Alaska Regional Renovations

Review Number: 310537

 

1) STATUS:   4-12-13 Comments to be addressed.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) P2.07         The lavatories P-5 and P-23 in the two public bathrooms opposite elevator #1 require mixing valves per UPC 413.1.

 

4) P2.07         BV-5 above Nurse Station 7-MS134 should be located on the 3/4" HWR branch coming from the NW corner.

 

5) P2.07         The pipe labeled as 2" CW coming from the shaft just south of elevator #5 should be labeled as 2" HW.

 

6) P0.01         Clarify the abbreviations G.N. and W.B. missing from the plumbing abbreviations.

 

7) P0.01         Seismic straps are missing from the water heater details required per IBC 508.2.

 

8) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.

 

 

 